CT Saturation Detection Based on the Distance Between Consecutive Points in the Plans Formed by the Secondary Current Samples and Their Difference-Functions

机译:基于二次电流采样形成的计划中连续点之间的距离及其差函数的CT饱和度检测

获取原文
获取原文并翻译 | 示例

摘要

This paper proposes a novel method to detect the saturation intervals where the secondary current of current transformers for protection purposes becomes distorted. The method is based on the analysis of plans formed by the secondary current samples $(i_{2})$ and their difference-functions (del[n]). The distance between consecutive points in these plans has a significant increase when saturation occurs, bucking the trend of the intervals without saturation. Two plans are considered: del[2] versus del[1] and del[3] versus del[2]. Besides the ease of implementation, the results indicate the effectiveness of the method to detect saturation intervals.
机译:本文提出了一种新的方法来检测饱和间隔,在此间隔中,用于保护目的的电流互感器的次级电流会失真。该方法基于对由次级电流采样$(i_ {2})$形成的计划及其差函数(del [n])的分析。当发生饱和时,这些计划中连续点之间的距离会显着增加,从而逆转了没有饱和的间隔趋势。考虑了两个计划:del [2]与del [1]和del [3]与del [2]。除了易于实施之外,结果还表明该方法检测饱和间隔的有效性。