A Novel Backup Distance Protection Scheme for Series-Compensated Transmission Lines

机译:串联补偿线路的新型备用距离保护方案

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Conventional distance protection applies the positive-sequence impedance to protect a line against short-circuit faults. Series-compensated lines may considerably change the positive-sequence impedance of the fault path and cause the distance relays to maloperate. To overcome this problem, the mutual impedance between phases of a transmission line is used for the design of a new distance protection scheme. The voltages and currents of both ends of the line are applied to compute the mutual impedance between the relay and the fault point. The proposed scheme has a reliable performance in protection against single-phase and double-phase-to-ground faults and, therefore, it can be used as a backup protection. Simulation results approve the efficiency of the proposed method in protection of series-compensated transmission lines.
机译:传统的距离保护采用正序阻抗来保护线路免受短路故障的影响。串联补偿线可能会大大改变故障路径的正序阻抗,并导致距离继电器倾斜。为了克服这个问题,传输线各相之间的互阻抗被用于设计新的距离保护方案。施加线路两端的电压和电流以计算继电器和故障点之间的互阻抗。所提出的方案在防止单相和双相接地故障方面具有可靠的性能,因此可以用作备用保护。仿真结果证明了该方法在串联补偿输电线路保护中的有效性。