Applications of Operational Modal Analysis to a Single-Phase Distribution Transformer

机译:模态分析在单相配电变压器中的应用

获取原文
获取原文并翻译 | 示例
           

摘要

Previous studies have shown that a transformer's modal characteristics can be identified by its internal electromagnetic excitations and are related to structural damage. These may be useful for diagnosing the causes of failure modes in power transformers during normal operation. Operational modal analysis (OMA) appears to be a suitable tool for this purpose. In this letter, the feasibility of OMA in identifying transformer modal parameters is discussed with a special focus on the mechanisms of natural excitation. OMA is also applied to a 10-kVA transformer with and without artificially designed structural damage. Good correlation is obtained between the results of OMA and those of experimental modal analysis.
机译:先前的研究表明,变压器的模态特性可以通过其内部的电磁激励来识别,并且与结构损坏有关。这些对于诊断正常运行期间电力变压器故障模式的原因可能很有用。操作模式分析(OMA)似乎是用于此目的的合适工具。在这封信中,讨论了OMA在识别变压器模态参数方面的可行性,并特别关注自然励磁的机理。 OMA还适用于有和没有人为设计的结构损坏的10 kVA变压器。 OMA的结果与实验模态分析的结果之间具有良好的相关性。