Determination of Breakdown Voltage Characteristics of 1'100 kV Disconnector for Modeling of VFTO in Gas-Insulated Switchgear

机译:确定用于气体绝缘开关设备中的VFTO的1'100 kV隔离开关的击穿电压特性

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents a method for determination of breakdown voltage characteristics (BDV) of a gas-insulated switchgear (GIS) disconnector. The method is applicable for modeling very fast transient overvoltages that are generated during the disconnector opening and closing operations. The method is based on full-scale measurements, as typically performed during the disconnector development and/or type tests. The method is first presented in a simplified, illustrative setting, and then applied for the full-scale measurement results obtained for an 1'100 kV disconnector design. The BDV determined is then applied for two 1'100 kV test setups as recently reported for the Wuhan (China) station. Selected test cases are simulated, analyzed, and validated with the use of the multispark modeling approach, with two BDV characteristics implemented: the nonlinear BDV obtained with the method presented here applied for the measurement results on the example 1'100 kV disconnector, and the linear BDV reported in the literature for the 1'100 kV disconnector used in the Wuhan GIS station.
机译:本文提出了一种确定气体绝缘开关设备(GIS)隔离开关的击穿电压特性(BDV)的方法。该方法适用于对隔离开关断开和闭合操作期间产生的非常快速的瞬态过电压进行建模。该方法基于通常在隔离开关开发和/或型式测试期间执行的满量程测量。该方法首先以简化的说明性设置呈现,然后应用于从1'100 kV隔离开关设计获得的满量程测量结果。然后,将确定的BDV应用于两个最近在武汉(中国)站报告的1'100 kV测试装置。使用多火花建模方法对选定的测试用例进行仿真,分析和验证,并实现了两个BDV特性:使用此处介绍的方法获得的非线性BDV用于示例1'100 kV隔离开关的测量结果,以及文献报道了武汉GIS站使用的1'100 kV隔离开关的线性BDV。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号