The paper presents a new adaptive 100% stator ground protection for high-impedance-grounded (HIG) synchronous generators. This is done by first examining reliability, that is, dependability and security of the most prominent conventional 3rd-harmonic voltage schemes. Using field data from various capacity industrial generators, it is shown that the conventional 3rd-harmonic differential voltage scheme, while being dependable, lacks security. Using the same field data, it is shown that the new adaptive scheme is a highly secure and sensitive scheme. Moreover, the new adaptive scheme is a zero-setting scheme which does not require any setting calculations, 3rd-harmonic voltage testings, or additional hardware.
机译:本文提出了一种适用于高阻抗接地(HIG)同步发电机的新型自适应100%定子接地保护。这是通过首先检查可靠性,即最突出的常规三谐波电压方案的可靠性和安全性来完成的。使用来自各种容量工业发电机的现场数据,表明传统的三次谐波差分电压方案虽然可靠,但缺乏安全性。使用相同的现场数据,表明新的自适应方案是高度安全和敏感的方案。此外,新的自适应方案是一种调零方案,不需要任何设置计算,三次谐波电压测试或其他硬件。