Accurate Impedance Calculation for Underground and Submarine Power Cables Using MoM-SO and a Multilayer Ground Model

机译:利用MoM-SO和多层接地模型精确计算地下和海底电力电缆的阻抗

获取原文
获取原文并翻译 | 示例
           

摘要

Accurate knowledge of the per-unit length impedance of power cables is necessary to correctly predict electromagnetic transients in power systems. In particular, skin, proximity and ground return effects must be properly estimated. In many applications, the medium that surrounds the cable is not uniform and can consist of multiple layers of different conductivity, such as dry and wet soil, water, or air. We introduce a multilayer ground model for the recently proposed MoM-SO method, suitable to accurately predict ground return effects in such scenarios. The proposed technique precisely accounts for skin, proximity, ground, and tunnel effects, and is applicable to a variety of cable configurations, including underground and submarine cables. Numerical results show that the proposed method is more accurate than analytic formulas typically employed for transient analyses, and delivers an accuracy comparable to the finite-element method (FEM). With respect to FEM, however, MoM-SO is over 1000 times faster, and can calculate the impedance of a submarine cable inside a three-layer medium in 0.10 s per frequency point.
机译:要正确预测电力系统中的电磁瞬变,必须准确了解电力电缆的每单位长度阻抗。特别是,必须正确估计皮肤,邻近区域和地面返回的影响。在许多应用中,电缆周围的介质并不均匀,并且可以由导电率不同的多层组成,例如干,湿土壤,水或空气。我们为最近提出的MoM-SO方法引入了多层地面模型,适用于在这种情况下准确预测地面返回效应。所提出的技术精确地考虑了趋肤,邻近,地面和隧道的影响,并且适用于各种电缆配置,包括地下和海底电缆。数值结果表明,所提出的方法比通常用于瞬态分析的分析公式更准确,并且可提供与有限元方法(FEM)相当的精度。但是,对于FEM,MoM-SO的速度要快1000倍以上,并且可以在每个频率点以0.10 s的速度计算三层介质内部的海底电缆的阻抗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号