Interturn Faults Detection of Transformers by Diagnosis of Neutral Current

机译:通过中性点电流诊断变压器匝间故障

获取原文
获取原文并翻译 | 示例

摘要

Interturn short-circuit faults are the leading cause of power transformer's failure. If not detected at the incipient stage, these faults usually develop into more severe faults that would result in irreversible damage to the transformer, unexpected outages, and consequential losses. This paper presents a transformer interturn fault detection system (TIFDS) for the detection of an interturn fault at the inception stage in power transformers. TIFDS is immune to supply voltage imbalance, constructional asymmetries, and instrumental errors. It also takes care of unequal load distribution. The TIFDS algorithm makes the transformer symmetrical in its entire three phases and sets primary-side neutral current to zero value. This is achieved by computing and applying various correction coefficients. However, under the interturn fault condition, TIFDS characterizes the behavior of neutral current. Simulation and experimentation studies are carried out on the 400/110-V, 3 × 2.5 kVA power transformer. Presented test results demonstrate the effectiveness of the proposed system.
机译:匝间短路故障是电力变压器故障的主要原因。如果在初期阶段未检测到这些故障,通常会发展为更严重的故障,这将导致对变压器的不可逆转的损坏,意外的断电和相应的损失。本文提出了一种变压器匝间故障检测系统(TIFDS),用于在电力变压器的初始阶段检测匝间故障。 TIFDS不受电源电压不平衡,结构不对称和仪器误差的影响。它还照顾到不平等的负载分配。 TIFDS算法使变压器在整个三相中对称,并将一次侧中性点电流设置为零值。这是通过计算和应用各种校正系数来实现的。但是,在匝间故障条件下,TIFDS表征了中性线电流的行为。在400 / 110-V,3×2.5 kVA电源变压器上进行了仿真和实验研究。提出的测试结果证明了所提出系统的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号