Voltage and current waveforms of transmission lines struck by lightning are calculated for use in back flashover analysis. Calculation by using equivalent circuits is the general practice, however, there are limited experimental results for reference to evaluate validity of developed equivalent circuits under various line conditions. Calculation results by numerical electromagnetic analysis can be used as references if they are proved reliable. In this paper, the voltage rises at a model of a 154 kV transmission line hit by lightning is calculated by Method of Moments (MoM) and FDTD for comparison. They solve Maxwell's equations by using different algorithms, so, if the calculated results by these methods reasonably agree under various line conditions, the results of these numerical analyses are regarded reliable. The calculated voltage and current waveforms by the two numerical methods agree well under a variety of footing resistance of transmission towers, thus the authors conclude that the calculated results by FDTD or MoM can be employed as references to evaluate validity of circuit models for back flashover analyses. Thus, the results calculated by circuit analysis are compared with those calculated by FDTD. The multistory tower model (Ishii model) better reproduces the voltage waveforms in a wide range of the footing resistance than simple circuit models of a tower, and can be easily tuned for further accuracy.
机译:计算通过闪电击中的传输线的电压和电流波形,用于回到闪络分析。使用等效电路计算是一般的实践,但是,有限的实验结果是参考,以评估在各种线条条件下开发的等效电路的有效性。通过数值电磁分析的计算结果可以用作证明可靠的参考。在本文中,通过闪电击中的154 kV传输线的模型在闪电模型中升高,通过时刻(MOM)和FDTD进行比较来计算。它们通过使用不同的算法解决Maxwell的方程,因此,如果这些方法在各种线条条件下合理地达成的计算结果,则这些数值分析的结果被认为是可靠的。通过两种数值方法计算的电压和电流波形在传输塔的各种基位电阻下非常恰好,因此作者得出结论,通过FDTD或MOM的计算结果可以用作评估回闪络分析的电路模型的有效性的参考。因此,与电路分析计算的结果与FDTD计算的结果进行了比较。多晶塔模型(ISHII模型)比塔的简单电路型号更好地再现电压的电压波形,并且可以轻松调整以进一步准确。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号