Third-harmonic based schemes are used to detect stator-ground faults in high-impedance grounded generators. These methods use third-harmonic voltage measures in the neutral and in terminals to detect faults. As third-harmonic voltage levels are different according to each generator and operational point, simulations, studies and tests need to be carried out to ensure that the chosen third-harmonic scheme is able to cover the portion closest to neutral while the conventional method (59GN) covers the portion closest to the stator winding terminals. This paper presents the solution of the third-harmonic generator model used for a stator-ground fault study in terms of the mesh currents and uses the derived equations to develop a third-harmonic based fault location method. The fault location method was tested over 1785 simulations and presented a maximum error of 0.004 p.u., determining the fault location accurately.
机译:基于三谐波的方案用于检测高阻抗接地发电机中的定子接地故障。这些方法使用中性和终端中的三谐波电压测量来检测故障。由于根据每个发电机和运行点的三谐波电压电平,需要进行仿真,研究和测试,以确保所选择的第三谐波方案能够覆盖最接近中性的常规方法(59Gn )覆盖最靠近定子绕组端子的部分。本文介绍了用于网状电流的定子接地故障研究的第三谐波发生器模型的解决方案,并使用导出的方程来开发基于三谐波的故障定位方法。故障定位方法超过1785年进行测试,并呈现为0.004 p.u的最大误差。,准确地确定故障位置。