Winding turn-to-turn fault (TTF) is one of the most reported reasons for transformer unplanned outage. If its occurrence is not detected at an early stage, it can develop into a costly phase-to-ground fault. In this paper, a novel algorithm based on the fault-related incremental currents is proposed to detect a low-level transformer TTF. This paper shows that the performance of the proposed method is independent of the transformer operating condition. Therefore, it is reliable even under the presence of power system transients such as the external faults. In addition, the proposed algorithm can be configured uniquely and easily. This feature prevents the algorithm from unnecessary trips. These trips can be considered as the general problem that most of the past presented methods face. The experimental tests used for verification of the algorithm show that, regardless of the transformer winding configuration and its pre-fault operating conditions, the proposed algorithm can accurately detect the TTF, which involves only 1% of the winding turns, in less than one cycle of power frequency. The reliable and secure performance of the proposed algorithm shows that it can be widely used in the advanced numerical relays.
机译:绕组匝间故障(TTF)是变压器意外中断的最常报告的原因之一。如果在早期阶段未检测到它的发生,则可能会发展成代价高昂的相间故障。本文提出了一种基于故障相关增量电流的新型算法,用于检测低电平变压器的TTF。本文表明,所提方法的性能与变压器的工作条件无关。因此,即使在存在外部故障等电力系统瞬变的情况下,它也是可靠的。另外,所提出的算法可以被唯一且容易地配置。此功能可防止算法不必要的跳闸。这些行程可被视为大多数过去提出的方法所面临的普遍问题。用于验证算法的实验测试表明,无论变压器绕组的配置及其故障前的运行条件如何,所提出的算法都可以在不到一个周期的时间内准确地检测出仅占绕组匝数1%的TTF。功率频率。所提算法的可靠性和安全性表明,该算法可广泛应用于高级数值继电器中。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号