首页> 外文期刊>The Korean journal of chemical engineering >Simplified risk assessment on fire hazard of LPG filling station
【24h】

Simplified risk assessment on fire hazard of LPG filling station

机译:石油气加气站火灾危险的简化风险评估

获取原文
获取原文并翻译 | 示例
       

摘要

Layer of protection analysis (LOPA) was conducted on the fire hazard of LPG filling stations. Scenarios were developed for jet fire, pool fire, and boiling liquid expanding vapor explosion (BLEVE). For each scenario, independent protection layers (IPLs) of the LPG station were identified and their frequencies were estimated. Risk matrix to determine the risk category was constructed, combining consequence and frequency of each scenario. Three additional IPLs were considered, such as a firewall between the tank lorry parking area and LPG facility, water deluge system for tank lorry, and excess flow shutdown valve for liquid pipeline to stop unexpected excess flow. Adding such IPLs could markedly reduce the risk to the facility.
机译:对液化石油气加气站的火灾危险进行了防护层分析(LOPA)。开发了喷射火,水池火和沸腾液体膨胀蒸气爆炸(BLEVE)的方案。对于每种情况,都确定了LPG站的独立保护层(IPL),并估计了它们的频率。结合每种情况的后果和发生频率,构建了确定风险类别的风险矩阵。还考虑了另外三个IPL,例如罐车停放区与LPG设施之间的防火墙,罐车的洒水系统以及用于液体管道的多余流量关闭阀以阻止意外的多余流量。添加此类IPL可以显着降低设施的风险。