Seismic Response of High Voltage Electrical Transformer-Bushing Systems

机译:高压电力变压器-套管系统的地震响应

获取原文
获取原文并翻译 | 示例
           

摘要

High voltage porcelain bushings mounted on transformers have shown vulnerability during past earthquakes. This is contrary to the generally good performance observed during shake table qualification testing of bushings anchored to a rigid base. The seismic vulnerability of porcelain bushings might be caused by the flexibility of transformer tanks and of bushing attachments. Current seismic qualification guidelines consider an amplification factor of 2.0 between the amplitude of the ground motion and the amplitude of the motion at the base of the bushing. This paper investigates numerically the dynamic response of porcelain bushings mounted on transformer tanks. The results of the numerical study show that large amplification occurs when the fundamental frequency of the porcelain bushing is tuned with the fundamental frequency of the transformer tank.
机译:在过去的地震中,安装在变压器上的高压瓷套管已经显示出脆弱性。这与锚定在刚性底座上的衬套的振动台鉴定测试期间通常观察到的良好性能相反。瓷套管的地震脆弱性可能是由于变压器油箱和套管附件的柔韧性引起的。当前的地震鉴定准则考虑到地面运动的振幅与衬套底部的运动的振幅之间的放大系数为2.0。本文从数值上研究了安装在变压器油箱上的瓷套管的动态响应。数值研究结果表明,当将瓷套管的基频与变压器箱的基频进行调谐时,会发生较大的放大。