首页> 外文期刊>Journal of Heat Transfer >Effect of Pin Tip Clearance on Flow and Heat Transfer at Low Reynolds Numbers
【24h】

Effect of Pin Tip Clearance on Flow and Heat Transfer at Low Reynolds Numbers

机译:低雷诺数时针尖间隙对流动和传热的影响

获取原文
获取原文并翻译 | 示例
           

摘要

Cylindrical pin fins with tip clearances are investigated in the low Reynolds number range 5 < Re_D < 400 in a plane minichannel. Five tip gaps are investigated ranging from a full pin fin (t* =0.0) to a clearance of t* = 0.4D*, where D* is the pin diameter. It is established that unlike high Reynolds number flows, the flow and heat transfer are quite sensitive to tip clearance. A number of unique flow effects, which increase the heat transfer performance, are identified. The tip gap affects the heat transfer coefficient by eliminating viscosity dominated end wall effects on the pin, by eliminating the pin wake shadow on the end walls, by inducing accelerated flow in the clearance, by reducing or impeding the development of recirculating wakes, and by redistributing the flow along the height of the channel. In addition, tip gaps also reduce form losses and friction factor. A clearance of t* =0.3D* was found to provide the best performance at Re_D < 100; however, for Re_D > 100, both t* =0.2D* and 0.3D* were comparable in performance.
机译:在平面微型通道中,在低雷诺数范围5 100,t * = 0.2D *和0.3D *的性能相当。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号