Single-phase liquid cooling in microchannels and microgaps has been successfully demonstrated for heat fluxes of~1 kW/cm~2 for silicon chips with maximum temperature below 100 °C. However, effectively managing localized hotspots in heterogeneous integration, which refers to the integration of various components that achieve multiple functionalities, entails further thermal challenges. To address these, we use a nonuniform pin-fin array. Single phase liquid-cooling performance of four silicon test chips, thermal design vehicles (TDVs), each with a nonuniform pin-fin array, are experimentally examined. We evaluate multiple combinations of hotspot and background heat fluxes using four background heaters aligned upstream to downstream, and one additional hotspot heater located in the center. We examine the thermal performance of cylindrical fin-enhanced TDVs and hydrofoil fin-enhanced TDVs, both with two designs: one with increased fin density around the hotspot only, and another with increased fin density spanning the entire width of the channel. The resulting heat flux ratio of the localized hotspot to background heaters varies from 1 to 5. TDVs with spanwise increased hydrofoil fin density (spanwise hydrofoil) exhibit the best thermal performance with 6% to 14% lower hotspot temperature than others. TDVs with spanwise increased cylindrical fin (cylindrical span-wise) maintain a balance between hotspot cooling performance and pressure drops. In general, as the temperature of the hotspot remains around 70 °C with a heat flux of 625 W/cm~2, the nonuniform fin-enhanced microgaps appears to be a promising hotspot thermal management approach. The pressure drop of hydrofoil spanwise chip is highest among all the cases.
机译:微通道和微吸入中的单相液体冷却已成功用于热通量为〜1kW / cm〜2的硅芯片,其最高温度低于100℃。然而,有效地管理异构集成中的局部热点,这是指实现多种功能的各种组件的集成,需要进一步的热挑战。要解决这些问题,我们使用不均匀的PIN鳍数组。通过实验检查单相液 - 冷却性能,四种硅试剂芯片,热设计车辆(TDV),每个具有非均匀销鳍阵列的型号。我们使用四个背景加热器评估热点和背景热通量的多种组合,使用上游到下游,以及位于中心的一个额外热点加热器。我们研究了圆柱形鳍片增强型TDV和水力纤维增强的TDV的热性能,两者都有两个设计:一个具有增加的翅片密度增加了热点,另一个具有跨越通道的整个宽度的翅片密度增加。所得到的热点与背景加热器的热通量比率从1到5中变化。TDVS具有翼展的水翼翅片密度(枝节水翼)表现出最佳的热性能,比其他热点温度低6%至14%。具有跨翼展的圆柱形翅片(圆柱形跨度)的TDVS在热点冷却性能和压降之间保持平衡。通常,随着热点的温度保持在70°C的热量为625W / cm〜2的热量,由于不均匀的纤维增强的微量菌似乎是一个有前途的热点热管理方法。水翼芯片的压降在所有情况下都是最高的。

著录项

  • 来源
    《Journal of Heat Transfer》 |2021年第3期|031501.1-031501.9|共9页
  • 作者单位

    George W. Woodruff School of Mechanical Engineering Georgia Institute of Technology 801 Ferst Drive Atlanta GA 30332-0405;

    School of Electrical and Computer Engineering Georgia Institute of Technology 777 Atlantic Drive Atlanta GA 30332-0405;

    School of Electrical and Computer Engineering Georgia Institute of Technology 777 Atlantic Drive Atlanta GA 30332-0405;

    George W. Woodruff School of Mechanical Engineering Georgia Institute of Technology 801 Ferst Drive Atlanta GA 30332-0405;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    hotspot; microgap cooling; heterogeneous pin-fin; thermal management;