Delayed fracture occurred to a temporary anchor supporting an overhead powerline during construction. The fracture resulted in loss of the overhead transmission line and resulted in a singe vehicle incident in the adjacent roadway. Post-failure analysis conducted as part of personal injury litigation revealed that the fracture was precipitated by a pre-existing weld related crack. Closed form and numerical stress analyses were conducted in order to assess the role of anchor installation in the failure, with the results indicating that installation was not conducted outside of the parameters intended by the anchor manufacturer.
机译:施工期间,支撑高架电力线的临时锚发生了延迟断裂。断裂导致高架传输线的损失,并导致一辆单车进入相邻的道路。作为人身伤害诉讼的一部分进行的故障后分析表明,断裂是由预先存在的与焊接相关的裂纹引起的。为了评估锚固装置在破坏中的作用,进行了封闭形式和数值应力分析,结果表明,锚固装置的安装并非超出锚固制造商预期的参数范围。