首页> 外文期刊>Journal of engineering and applied science >SIMULATION OF CHLORINE DECAY IN WATER DISTRIBUTION NETWORKS USING WATERCAD-CASE STUDY
【24h】

SIMULATION OF CHLORINE DECAY IN WATER DISTRIBUTION NETWORKS USING WATERCAD-CASE STUDY

机译:WaterCAD-Case模拟模拟供水管网中氯的衰减

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Deterioration of water quality in distribution networks has a great impact on human health and public acceptance of tap water reaching them. Residual chlorine should be maintained through network pipes to prevent contamination and microbial regrowth. This paper investigates the ability of WaterCAD V8XM to simulate residual chlorine decay through water networks, taking water-age analyses into consideration, and assesses the feasibility of using it as a measuring and controlling tool to estimate . and predict chlorine concentration at different water network points. A study was performed on drinking water network of 6th of October city, where field measurements were done, while data required as program inputs were taken from the daily records of the 6th of October and El-Shaikh Zayed WTPs. The network model was calibrated to minimize error in program results. Errors were evaluated using statistical analyses. The calculated concentrations by the calibrated model were very close to the actual concentrations measured in field at different sampling points for different sampling days. Moreover, WaterCAD showed that for the water network concerned in this study there is high possibility that chlorine concentrations become lower than 0.20 mg/L at network extremities when water-age exceeded 10 hrs, which may call for using re-chlorinating points to raise safety margins.
机译:配水网络中水质的恶化对人类健康和公众接受自来水的接受程度都有很大影响。氯气应通过网络管道进行维护,以防止污染和微生物再生。本文研究了WaterCAD V8XM通过水网络模拟残余氯衰减的能力,并考虑了水龄分析,并评估了将其用作测量和控制工具进行估算的可行性。并预测不同水网点的氯浓度。在10月6日城市的饮用水网络上进行了一项研究,在该网络上进行了现场测量,而从10月6日和El-Shaikh Zayed WTP的每日记录中获取了程序输入所需的数据。对网络模型进行了校准,以最大程度减少程序结果中的错误。使用统计分析评估错误。校准模型计算出的浓度非常接近在不同采样日不同采样点现场测量的实际浓度。此外,WaterCAD显示,对于本研究中涉及的水网络,当水龄超过10小时时,网络末端的氯浓度极有可能低于0.20 mg / L,这可能要求使用重新加氯点来提高安全性利润。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号