首页> 外文期刊>Journal of energy and power engineering >Comparison Voltage across Insulator Strings of 69 kV and 24 kV Lines due to Lightning Strokes to Top Pole and Mid Span
【24h】

Comparison Voltage across Insulator Strings of 69 kV and 24 kV Lines due to Lightning Strokes to Top Pole and Mid Span

机译:比较顶极和中跨的雷击产生的69 kV和24 kV线路的绝缘子线两端的电压

获取原文
获取原文并翻译 | 示例
           

摘要

This paper analyzes the effects of the voltage across insulator of 69 kV and 24 kV lines installed on the same pole. The case studies illustrated the lightning strike to direct top pole and mid span of ground wire using the ATP-EMTP (Alternative Transient Program-Electromagnetic Transient Program). The results found that when lightning strike the voltage across the 69 kV line insulator at mid span is 1.55 times and 1.34 times higher than at top pole when the front time is 0.25/100 us and 10/350 us, respectively. When lightning strike the voltage across the 24 kV line at mid span is 1.04 times and 0.64 times higher than at top pole when the front time is 0.25/100 us and 10/350 us, respectively. So the effect of lightning strike is more severe at mid span than at the direct top pole, especially for the 69 kV insulator.
机译:本文分析了安装在同一极上的69 kV和24 kV线路的绝缘子两端的电压的影响。案例研究说明了使用ATP-EMTP(替代瞬态程序-电磁瞬态程序)将雷电直接引到地线的上极和中跨。结果发现,当雷击时,前跨时间分别为0.25 / 100 us和10/350 us时,跨度中间的69 kV线路绝缘子两端的电压分别比顶部极高1.55倍和1.34倍。当雷击时,跨度在中跨24 kV线路上的电压分别比前端时间为0.25 / 100 us和10/350 us时的顶极高1.04倍和0.64倍。因此,雷击的影响在中跨比在直接顶极更严重,尤其是对于69 kV绝缘子。