Thermally Aware, Energy-Based Load Placement in Open-Aisle, Air-Cooled Data Centers

机译:热感知,基于能量的负载放置在开放式通道,风冷数据中心中

获取原文
获取原文并翻译 | 示例
           

摘要

This paper introduces a methodology for developing a reduced order model, using proper orthogonal decomposition (POD), to predict the IT rack's inlet temperature distribution within a raised floor air-cooled data center. The method used in this paper uses a limited set of computational fluid dynamics data at different useful IT levels and tile airflow fractions. The model was able to reconstruct these datasets to with 0.16 ℃ rms error and interpolate successfully for alternative configurations that were not included in the original dataset. The reduced order model can produce the temperature distribution in the data center in a fraction of a second on a standard personal computer. Several practical IT load placement options in open-aisle, air-cooled data centers, based on either geometrical traits of the data center, a prior physics-based knowledge of the airflow and temperature patterns or measurements that are easily obtainable during operation, are considered. The outcome of this work is the development of a robust set of guidelines that facilitate the energy efficient placement of the IT load amongst the operating servers in the data center. This work found that a robust approach was to use real-time temperature measurements at the inlet of the racks to remove the unnecessary IT load from the servers with the warmest inlet temperature. This strategy shows superior performance to the other strategies studied. The study considered the holistic optimization of the data center and cooling infrastructure for a range of data center IT utilization levels. The results showed that allowing for significant reductions in the supply airflow rate proved superior to providing a higher supply air temperature to meet the IT equipment's inlet air temperature constraint.
机译:本文介绍了一种使用适当的正交分解(POD)来开发降阶模型的方法,以预测高架地板风冷数据中心内IT机架的入口温度分布。本文使用的方法在不同的有用IT级别和瓷砖气流比例下使用了一组有限的计算流体动力学数据。该模型能够将这些数据集重建为具有0.16℃rms误差,并且可以成功插入原始数据集中未包含的替代配置。降阶模型可以在标准个人计算机上在几分之一秒内产生数据中心内的温度分布。根据数据中心的几何特性,对气流和温度模式或操作过程中易于获得的基于物理的先验知识,考虑了开放式风冷数据中心中的几种实用IT负载放置选项。这项工作的结果是制定了一套可靠的指南,这些指南有助于在数据中心的运营服务器之间高效地放置IT负载。这项工作发现,一种可靠的方法是在机架的入口处使用实时温度测量,以从入口温度最高的服务器上消除不必要的IT负载。该策略显示出优于其他研究策略的性能。该研究考虑了针对一系列数据中心IT利用率水平的数据中心和冷却基础架构的整体优化。结果表明,允许大幅降低送风量优于提供更高的送风温度来满足IT设备的进风温度限制。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号