Allowable capacity of ACDG considering inverse time overcurrent protection

机译:考虑反时限过电流保护的ACDG的允许容量

获取原文
获取原文并翻译 | 示例
       

摘要

The integration of distributed generation (DG) into distribution system has a lot of impacts on the original current protection. The influences of alternating current (AC)-connected DG on inverse time overcurrent protection are analyzed in this paper. Based on the setting and coordination principles of protection, four constraints for the allowable capacity of AC-connected DG are advised to ensure the reliability of protection.A specific example is given to show the calculation process. In order to increase the allowable capacity,some improvement methods are proposed. Two different integration points are compared, and finally the one requiring less of protection modification is chosen. The effectiveness of the measures is also verified through the example. Copyright © 2014 John Wiley & Sons, Ltd.
机译:将分布式发电(DG)集成到配电系统中会对原始电流保护产生很大影响。本文分析了交流电接入的DG对反时限过电流保护的影响。根据保护的设置和协调原则,建议对交流并网DG的允许容量进行四个限制,以确保保护的可靠性。给出一个具体的例子来说明计算过程。为了增加允许容量,提出了一些改进方法。比较了两个不同的积分点,最后选择了需要较少保护修改的积分点。该示例还验证了这些措施的有效性。版权所有©2014 John Wiley&Sons,Ltd.