A new algorithm to prevent maloperation of distance protection zone 3 during wide‐area disturbances

机译:一种防止广域干扰中距离保护区3误操作的新算法

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents a new algorithm to avoid cascading tripping of interconnected transmission lines caused by maloperation of zone 3 distance relay during major power system disturbances. Blocking of zone 3 distance relay and the application of static var compensator controllers are the 2 corrective actions that proposed algorithm use to protect the power system from cascade tripping. Distance relay zone 3 blocking is achieved using real-time information about the balance between generation and load in each area of the power system. However, the static var compensator controller allows injecting, rapidly and efficiently, necessary reactive power in the system to mitigate the disturbance development during the blockage of the distance relay protection. Results of dynamic simulation on 400kV Turkish transmission system, using SECRE software, are presented to demonstrate the effectiveness of the proposed algorithm. Simulation results clearly indicate that the use of this algorithm can improve reliability of zone 3 distance relay operation, enhance the stable operation of power system, and can limit the spread of cascading outages during wide-area disturbance.
机译:本文提出了一种新的算法,可以避免在主要电力系统扰动期间因区域3距离继电器误操作而导致的互连输电线路级联跳闸。区域3距离继电器的阻塞和静态无功补偿器控制器的应用是所提出的算法用来保护电力系统免受级联跳闸影响的2种纠正措施。使用有关电力系统每个区域中发电与负荷之间平衡的实时信息,可以实现距离继电器3区的闭锁。但是,静态无功补偿器控制器允许在系统中快速有效地注入必要的无功功率,以减轻距离保护装置阻塞期间的干扰发展。提出了使用SECRE软件对400kV土耳其输电系统进行动态仿真的结果,以证明该算法的有效性。仿真结果清楚地表明,使用该算法可以提高三区距离继电器的可靠性,增强电力系统的稳定运行,并可以限制广域扰动时级联断电的扩散。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号