首页> 外文期刊>European Transactions on Electrical Power >Distance protection blocking and re‐opening scheme in multi‐machine power system oscillation scenes
【24h】

Distance protection blocking and re‐opening scheme in multi‐machine power system oscillation scenes

机译:多机电力系统振荡场景中的距离保护闭锁和重开方案

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

In view of frequent multi-machine power system oscillations in power grid which may cause traditional oscillation blocking and re-opening schemes to be completely invalid, a distance protection oscillation blocking and re-opening scheme in multi-machine power system oscillation scenes is proposed in this paper. First, the ride-through trajectory of measured impedance in multi-machine power system oscillation cases and its effect on the operation characteristic of distance protection is analyzed, and the oscillation blocking scheme is formed by combining the operation status information of protection components on 2 line ends. And then, in the oscillation blocking duration, by calculating the estimated error of the dynamic phasor of measured current at the relaying point, the protection re-opening scheme for symmetrical fault during oscillation is established. Finally, simulation tests on PSCAD in 3-machine system and IEEE 39-bus system verify that the proposed scheme could reliably block the protection when oscillation occurs in multi-machine power system, and re-open the protection accurately and reliably when symmetrical fault occurs during oscillation.
机译:针对电网中频繁出现的多机电网振荡问题,可能导致传统的振荡闭锁和重开方案完全失效的问题,提出了一种在多机电网振荡场景中的距离保护振荡闭锁和重开方案。这篇报告。首先,分析了多机电力系统振荡情况下测得的阻抗的穿越轨迹及其对距离保护动作特性的影响,并结合了两行保护元件的动作状态信息,形成了振荡阻断方案。结束。然后,在振荡闭塞持续时间内,通过计算中继点测得电流动态相量的估计误差,建立了振荡过程中对称故障的保护重开方案。最后,在3机系统和IEEE 39总线系统的PSCAD上进行的仿真测试证明,该方案可以在多机电力系统发生振荡时可靠地阻止保护,并在出现对称故障时准确而可靠地重新打开保护。在振荡期间。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号