A concern in the design and operation of closed, two-phase therosyphons (CTPTs)is determining the initial filling ratio of the working fluid, as a function of CTPT dimensions, type and vapor temperature of working fluid and power throughput, to maximize performance, while avoiding potential dryout in the evaporator section. A one-dimensional, steady-state model is developed for determining the operation envelopes of CTPTs, in terms of the above parameters. The CTPT operation envelope is basically an enclosure with three boundaries. The lower boundary corresponds to when the liquid film thickness in the evaporator reaches a critical value-beyond it the liquid film could dry out-while the upper boundary coorresponds to when the expanding liquid pool, due to boiling, fills the entire evaporator.
机译:闭式两相式交响管(CTPT)的设计和操作中的一个问题是,根据CTPT尺寸,工作流体的类型和蒸气温度以及功率通过量来确定工作流体的初始填充率,以最大程度地提高性能,同时避免蒸发器部分可能变干。根据上述参数,开发了一种一维稳态模型来确定CTPT的运行范围。 CTPT操作包络基本上是一个具有三个边界的外壳。下边界对应于蒸发器中的液膜厚度达到临界值时(超过该临界值时,液膜可能会变干),而上边界对应于由于沸腾而膨胀的液池充满整个蒸发器时的上限。