首页> 外文期刊>International Journal of Heat and Mass Transfer >A comparative evaluation of two different heat-recovery schemes as applied to a two-bed adsorption chiller
【24h】

A comparative evaluation of two different heat-recovery schemes as applied to a two-bed adsorption chiller

机译:对两床吸附式制冷机的两种不同的热回收方案的比较评估

获取原文
获取原文并翻译 | 示例
       

摘要

This study investigates the efficiency of two distinct heat-recovery schemes as applied to the two-bed silica gel-water adsorption chiller. Performance predictions stemming from an experimentally verified distributed-parameter model compare favorably with the experimental results at various operating conditions. Our study highlights the pivotal role played by heat-recovery schemes to ameliorate the chiller performance and substantially improve the coefficient of performance (or COP). The two different schemes essentially offer the same cooling capacity and similar COP boosting capability. In the studied working conditions of a two-bed adsorption chiller, the difference in COP by using the two schemes is less than 5%.
机译:这项研究调查了应用于两床硅胶-水吸附式冷却器的两种不同的热回收方案的效率。由实验验证的分布参数模型得出的性能预测与各种操作条件下的实验结果均具有可比性。我们的研究强调了热量回收计划在改善冷水机组性能并显着提高性能系数(COP)方面所起的关键作用。两种不同的方案实质上提供了相同的冷却能力和相似的COP提升能力。在研究的两床吸附式冷却器的工作条件下,使用两种方案的COP差异小于5%。