首页> 外文期刊>International Journal of Heat and Mass Transfer >Comparison of a 2D axisymmetric CFD model of a natural draft wet cooling tower and a 1D model
【24h】

Comparison of a 2D axisymmetric CFD model of a natural draft wet cooling tower and a 1D model

机译:自然通风湿式冷却塔的二维轴对称CFD模型与一维模型的比较

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The performance predictions of a simple one-dimensional natural draft wet cooling tower (NDWCT) model and a two-dimensional axisymmetric numerical model are compared under a range of design parameters. The two-dimensional model has the ability to resolve radial non-uniformities across the tower which the one-dimensional model only computes as a bulk averaged value. The difference between the overall cooling range predicted by the two models is generally less than 2%, with no divergence in the agreement between the methods with respect to any design parameter.
机译:在设计参数范围内,比较了简单的一维自然通风湿式冷却塔(NDWCT)模型和二维轴对称数值模型的性能预测。二维模型具有解决整个塔架上径向不均匀性的能力,而一维模型仅将其计算为体积平均值。两种模型预测的总体冷却范围之间的差异通常小于2%,并且方法之间在任何设计参数方面的一致性都没有差异。