In testing transformer oils for durability, it is desirable to use typical transformer operating conditions with appropriate allowances for factor of safety against temperature and voltage. The kinetics of degradation of used type II transformer oil with original flash point of 148℃, pour point of < -51℃, and water content of 4 ppm was investigated. Assuming that the oil temperature in models Pr_(01) and Pr_(02) transformers rises to 60-85℃ with maximum operating voltage of 230 KV, these conditions were simulated in the laboratory using DTS-100D oil tester for voltage breakdown, HKV 400 series High Viscosity Bath, and EM300/CX1 heater.
机译:在测试变压器油的耐久性时,理想的是使用典型的变压器工作条件,并留有适当的余量,以保证温度和电压的安全性。研究了用过的Ⅱ型变压器油的降解动力学,其原始闪点为148℃,倾点<-51℃,水含量为4ppm。假设Pr_(01)和Pr_(02)型变压器中的油温上升到60-85℃,最大工作电压为230 KV,则在实验室中使用DTS-100D油压测试仪(HKV 400)模拟了这些条件系列高粘度浴和EM300 / CX1加热器。