首页> 外文期刊>International Journal of Electrical Power & Energy Systems >Differential energy based relaying for thyristor controlled series compensated line
【24h】

Differential energy based relaying for thyristor controlled series compensated line

机译:晶闸管控制串联补偿线的基于差能的继电保护

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The paper presents a differential energy based protection scheme for transmission line including Thyristor Controlled Series Compensator (TCSC) using time-frequency transform such as S-transform. Initially the current at sending and receiving ends are retrieved and processed through the time-frequency transform such as S-transform to generate the time-frequency patterns (frequency contours). Spectral energy content of the frequency contours of both current signals are calculated and differential energy is computed to register the fault patterns in the transmission line. The tripping signal can be issued based on a set threshold, within two cycles from the fault inception, meeting the speed criteria of the digital relay. The results indicate that the differential energy based protection scheme can reliably detect the fault patterns in TCSC line including wide variations in operating conditions of the faulted power network.
机译:本文提出了一种基于差分能量的输电线路保护方案,该方案包括采用时频变换(例如S变换)的晶闸管控制串联补偿器(TCSC)。最初,通过诸如S变换的时频变换对发送和接收端的电流进行检索和处理,以生成时频模式(频率轮廓)。计算两个电流信号的频率轮廓的频谱能量含量,并计算差分能量以将故障模式记录在传输线中。跳闸信号可以在故障发生后的两个周期内基于设置的阈值发出,满足数字继电器的速度标准。结果表明,基于差动能量的保护方案可以可靠地检测TCSC线路中的故障模式,包括故障电网的工作条件的广泛变化。