首页> 外文期刊>International journal of electrical power and energy systems >Capacitive discharge based transient analysis with fault detection methodology in DC system
【24h】

Capacitive discharge based transient analysis with fault detection methodology in DC system

机译:直流系统中基于电容放电的瞬态分析与故障检测方法

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Multi-terminal DC (MTDC) system based on voltage source converter (VSC) promises a new opportunity for bulk power transmission but it is still met with dire protection issues. This paper presents a transient analysis based on DC-link capacitive discharge which can be leveraged to design a fault detection method. Under certain critical fault conditions, the fault-induced transient can be quite weak for fault detection to work properly. However, the proposed method is minimally influenced by the fault location and resistance. The fault detection time can be kept within 1 ms, which is well-suited to the requirement of the DC circuit breaker. Another important feature of this method is the ability to distinctly recognize the bus fault and external faults, such as AC fault and sudden blocking of gate signal. Besides that, it only requires the local measurement at the terminal to perform necessary computations. The fault detection is tested on a simulation model developed in PSCAD/EMTDC and experimental model, from which different fault types and conditions are investigated. For fair evaluation, the performance of this method on MTDC system is compared with di/dt method.
机译:基于电压源转换器(VSC)的多端子DC(MTDC)系统为大功率输电提供了新的机遇,但仍然面临严重的保护问题。本文提出了一种基于直流母线电容性放电的瞬态分析方法,可用于设计故障检测方法。在某些关键故障条件下,故障引起的瞬变可能非常弱,无法使故障检测正常工作。然而,所提出的方法受故障位置和电阻的影响最小。故障检测时间可以保持在1 ms以内,非常适合直流断路器的要求。该方法的另一个重要特征是能够清楚地识别总线故障和外部故障,例如AC故障和门信号突然阻塞。除此之外,只需要在终端进行本地测量就可以进行必要的计算。在PSCAD / EMTDC中开发的仿真模型和实验模型上测试了故障检测,从中研究了不同的故障类型和条件。为了公平评估,将该方法在MTDC系统上的性能与di / dt方法进行了比较。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号