Experimental investigation of turbulent heat transfer by counter and co-swirling flow in a flat tube fitted with twin twisted tapes

机译:在装有双扭带的扁平管中通过逆向和涡流进行湍流传热的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

The use of inserts has gained extensive attention due to their role in improving the efficiency of thermal systems. In this study, an experimental investigation was conducted to explore the effect of twin counter and co-twisted tapes on heat transfer rate (Nu), friction factor (f) and thermal enhancement index (η). The twin counter twisted tapes (CTT) and twin co-twisted tapes (CoTT) were used as swirl flow generators in a test section. The tests were conducted using the CTT and CoTT with three different twist ratios (H/D) = 5,10 and 15) for Reynolds numbers range between 7200 and 32,400 under uniform heat flux conditions. The results show that Nusselt number (Nu), friction factor (f) and thermal enhancement index (η) increase with decreasing twist ratio (H/D) and the CTT is more efficient than the CoTT for heat transfer enhancement. Within the scope of this study, heat transfer rates in the flat tube fitted with the CTT are around 225% and 61% higher than those with the CoTT and plain flat tube, respectively. The maximum thermal enhancement index (η) obtained at the constant flow rate by the CTT with H/D = 5,10 and 15, are 1.58,1.44 and 1.15 respectively, while those obtained using the CoTT with the same range of H/D are 1.43, 1.19 and 1.04, respectively. Furthermore, the empirical correlations of the heat transfer (Nu), friction factor (f) and thermal enhancement index (η) are also reported.
机译:由于嵌件在提高热力系统效率方面的作用,因此备受关注。在这项研究中,进行了一项实验研究,以探索双反面和双绞带对传热速率(Nu),摩擦系数(f)和热增强指数(η)的影响。在测试部分中,将双反扭曲带(CTT)和双共扭曲带(CoTT)用作旋流发生器。使用CTT和CoTT在均匀的热通量条件下使用三种不同的扭曲比(H / D)= 5,10和15进行测试,雷诺数范围在7200和32,400之间。结果表明,随着扭转比(H / D)的降低,努塞尔数(Nu),摩擦系数(f)和热增强指数(η)均增加,并且CTT比CoTT更有效率。在这项研究的范围内,装有CTT的扁管的传热率分别比CoTT和普通扁管的传热率高约225%和61%。 H / D = 5,10和15的CTT在恒定流量下获得的最大热增强指数(η)分别为1.58、1.44和1.15,而使用CoTT在相同H / D范围内获得的最大热增强指数(η)分别为1.43、1.19和1.04。此外,还报告了传热(Nu),摩擦系数(f)和热增强指数(η)的经验相关性。

著录项

  • 来源
  • 作者单位

    Faculty of Mechanical Engineering, Universiti Malaysia Pahang, 26600 Pekan, Pahang Malaysia;

    Faculty of Mechanical Engineering, Universiti Malaysia Pahang, 26600 Pekan, Pahang Malaysia,Automotive Engineering Centre, Universiti Malaysia Pahang, 26600 Pekan, Pahang, Malaysia;

    Faculty of Mechanical Engineering, Universiti Malaysia Pahang, 26600 Pekan, Pahang Malaysia,Automotive Engineering Centre, Universiti Malaysia Pahang, 26600 Pekan, Pahang, Malaysia;

    Faculty of Mechanical Engineering, Universiti Malaysia Pahang, 26600 Pekan, Pahang Malaysia,Automotive Engineering Centre, Universiti Malaysia Pahang, 26600 Pekan, Pahang, Malaysia;

    Tarbiat Modares University, Jalale-E-Aleahmad Highway, Tehran, Iran;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Heat transfer coefficient; Friction factor; Twin twisted tape; Flat tube;

    机译:传热系数;摩擦系数;双绞带;扁管;