One of the more difficult problems to solve in industrial plants is how to identify and eliminate ground faults in a high-resistance ground (HRG) system. This is because ground-fault conditions in these systems do not draw enough current to reliably trigger fault current sensors in the drive. This article develops an approach to identify the ground-fault location in HRG systems using voltage sensing, rather than current sensing techniques, inside an adjustable speed drive (ASD). This approach consists of a simple analog circuit and digital signal processing technique to detect a fault condition, as well as to identify the fault location, be it on the load motor side, inside the ASD, or ac line side. The use of this ground-fault identification method is also extended and discussed for application to multiple drive lineups.
机译:在工厂中要解决的最困难的问题之一是如何识别和消除高电阻接地(HRG)系统中的接地故障。这是因为这些系统中的接地故障条件不会汲取足够的电流来可靠地触发驱动器中的故障电流传感器。本文提出了一种在变速驱动器(ASD)内使用电压感应而非电流感应技术来识别HRG系统中接地故障位置的方法。这种方法由简单的模拟电路和数字信号处理技术组成,以检测故障状况并确定故障位置,无论是在负载电动机侧,ASD内部还是在交流线路侧。接地故障识别方法的使用也得到扩展和讨论,以应用于多个驱动器产品系列。