首页> 外文期刊>Industry Applications Magazine, IEEE >Short-Circuit Current Ratings: Key Considerations for the Safety of Commercial and Industrial Electrical Systems
【24h】

Short-Circuit Current Ratings: Key Considerations for the Safety of Commercial and Industrial Electrical Systems

机译:短路电流额定值:商业和工业电气系统安全的主要考虑因素

获取原文
获取原文并翻译 | 示例
           

摘要

The interrupting rating (ir) and short-circuit current rating (sccr) of equipment is a key consideration for the instal-lation of equipment in electrical distribution systems. to emphasize this consideration, the 2005 national electrical code (nec) added sccr marking requirements for various types of equipment that previously was not required to be marked. the marked sccr of equipment is determined by the product standards as part of the listing and labeling process of the equipment or an approved method, such as uL 508a, UL Standard for Safety for Industrial Control Panels. uL 508a supplement sB is an analytical (nontested) method of determining the SCCR of industrial control panels. This method basically determines the "weak link" of all power circuit components in the industrial control panel and the low-est-rated component then determines the assembly rating. Additional changes to the 2011 NEC have been made to ensure that equipment has sufficient SCCRs for the available short-circuit (fault) current where the equipment is installed.
机译:设备的中断额定值(ir)和短路电流额定值(sccr)是在配电系统中安装设备的关键考虑因素。为了强调这一点,2005年国家电气法规(nec)对以前不需要标记的各种类型的设备增加了sccr标记要求。设备的标记sccr由产品标准确定,作为设备清单和标签过程或批准的方法的一部分,例如uL 508a,UL工业控制面板安全标准。 uL 508a补充剂sB是确定工业控制面板SCCR的分析方法(未经测试)。该方法基本上确定了工业控制面板中所有电源电路组件的“弱连接”,然后由最低额定值的组件确定装配额定值。对2011 NEC进行了其他更改,以确保设备具有足够的SCCR,以适应安装设备的可用短路(故障)电流。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号