首页> 外文期刊>Industry Applications Magazine, IEEE >Undercurrent Protection Power System: A Novel Ground-Fault Protection Relay Scheme
【24h】

Undercurrent Protection Power System: A Novel Ground-Fault Protection Relay Scheme

机译:欠电流保护电源系统:新型的接地故障保护继电器方案

获取原文
获取原文并翻译 | 示例
           

摘要

THE NATIONAL ELECTRICAL CODE (NEC) [1] requires that ground-fault protection of equipment be provided when the building service disconnecting rating becomes 1,000 A or higher. To meet such a requirement, generally, the main service breaker is specified with ground-fault protection capability. This type of breaker provides ground-fault protection for faults occurring on its load side but not for faults occurring on the line side. Such ground faults may be on the building transformer secondary windings, including the secondary feeder cable terminations at both ends. This article describes a ground-fault protection relay scheme that can provide low-level arcing, ground-fault current protection of the building transformer secondary, including secondary feeder cables. A discussion is included on meeting the design requirements of NEC 705.12 for the building's 480Y/277V main switchboard (MSB) bus rating when a photovoltaic (PV) ac inverter connection is implemented using a dedicated circuit breaker inside the switchboard.
机译:国家电气法规(NEC)[1]要求当建筑物服务断开额定值达到1,000 A或更高时,应为设备提供接地故障保护。为了满足这样的要求,通常,指定主服务断路器具有接地故障保护功能。这种断路器为在其负载侧发生的故障提供接地故障保护,但对于线路侧发生的故障则不提供接地保护。这种接地故障可能出在建筑物变压器的次级绕组上,包括两端的次级馈线电缆终端。本文介绍了一种接地故障保护继电器方案,该方案可以为建筑物变压器次级(包括次级馈线)提供低水平电弧放电,接地故障电流保护。当使用配电盘内部的专用断路器实现光伏(PV)交流逆变器连接时,将讨论满足建筑物的480Y / 277V主配电盘(MSB)额定值的NEC 705.12的设计要求。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号