The authors discusses the effects of switching low inductive currents with 138 kV SF/sub 6/ breakers in a petrochemical plant. Switching transients are believed to have contributed to the failure of a 13.8 kV PT and a 13.8 kV air magnetic circuit breaker. The high-frequency transient surge can transfer across a transformer due to transformer capacitances between the high- and low-voltage windings. The electromagnetic transient program system (ETPS) model and different case studies are discussed with the effect of different transformer winding capacitances. The interruption mechanism of low inductive currents is also described. This analysis demonstrates the need to conduct switching transient studies and the need for surge arresters on transformer secondary terminals under certain system conditions.
机译:作者讨论了在石化厂中用138 kV SF / sub 6 /断路器切换低感应电流的影响。开关瞬变被认为是造成13.8 kV PT和13.8 kV空气电磁断路器故障的原因。由于高压绕组和低压绕组之间的互感器电容,高频瞬变电涌会在整个互感器上传递。在不同的变压器绕组电容的影响下,讨论了电磁暂态程序系统(ETPS)模型和不同的案例研究。还描述了低感应电流的中断机理。该分析表明,在某些系统条件下,需要进行开关暂态研究,并且需要在变压器次级端子上使用电涌放电器。