首页> 外文期刊>IEEE Transactions on Industry Applications >Induced voltages on fence wires and pipelines by AC power transmission lines
【24h】

Induced voltages on fence wires and pipelines by AC power transmission lines

机译:交流输电线路在围栏导线和管道上的感应电压

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

A method is developed for calculating the induced voltages on fence wires/pipelines underneath AC power transmission lines. The method is based on the charge simulation technique and takes into account the disturbances of the electric field and potential due to the presence of the fence wire/pipeline underneath the line. The calculated values of the induced voltage on fence wires are compared with those measured before. Induced voltages on pipelines underneath 230- and 380-kV lines are measured, correlated to the calculated values and discussed in the light of electric field induction on objects adjacent to AC power transmission lines.
机译:开发了一种用于计算交流输电线路下方的栅栏/管道上的感应电压的方法。该方法基于电荷模拟技术,并考虑了由于线下围栏线/管道的存在而引起的电场和电势的干扰。将围栏导线上感应电压的计算值与之前测得的值进行比较。测量230-kV和380-kV线路下方管道上的感应电压,将其与计算值相关联,并根据与交流输电线路相邻的物体上的电场感应进行讨论。