首页> 外文期刊>IEEE Transactions on Industry Applications >Considerations for generator ground-fault protection in midsize cogeneration plants
【24h】

Considerations for generator ground-fault protection in midsize cogeneration plants

机译:中型热电厂的发电机接地故障保护注意事项

获取原文
获取原文并翻译 | 示例
           

摘要

Generator ground-fault protection aspects are analyzed for midsize cogeneration plants. In these plants, the generators may be connected to a common generator bus. The overall bus-connected system should be considered when applying generator high-resistance grounding schemes. Calculations are reviewed for sizing generator neutral-ground resistance and evaluating third harmonic originated in the scheme. The relevant applications of third harmonics in applying 100% stator ground-fault protection schemes are examined. Practical considerations are presented for establishing selectivity of ground-fault protection schemes in the case of a common generator bus.
机译:对中型热电联产厂的发电机接地故障保护方面进行了分析。在这些工厂中,发电机可以连接到公共发电机总线。在应用发电机高电阻接地方案时,应考虑整个母线连接系统。审查了用于确定发电机中性点接地电阻大小和评估源自该方案的三次谐波的计算。研究了三次谐波在应用100%定子接地故障保护方案中的相关应用。在建立通用发电机母线的情况下,提出了建立接地故障保护方案选择性的实际考虑。