An arc fault is the discharge of electricity through the air between two conductors creating large quantities of heat and light. It is widely accepted that there are many variables which affect the behavior of an arc in real switchboards, and thus, understanding the phenomena is difficult. This paper is based upon the results of several years of arc testing with circuits from 155 Vdc to three-phase 450 Vac and at power levels from tens of kilowatts to several megawatts. The goals of the testing were to understand the general behavior of arcing faults in low-voltage switchboards—well enough to predict the motion of arcs—and to design electronic monitoring systems that are capable of protecting switchboards against arcs. This paper will focus on the arc behavior, whereas our other papers will discuss its implications upon forensic investigations and upon the arc-fault protective systems.
机译:电弧故障是指通过两条导体之间的空气放电产生大量的热和光。众所周知,在实际的配电盘中,有许多变量会影响电弧的行为,因此,很难理解这种现象。本文基于在155 Vdc至三相450 Vac的电路以及数十千瓦至几兆瓦的功率水平下进行的多年电弧测试的结果。该测试的目的是了解低压配电盘中电弧故障的一般行为-足以预测电弧的运动-并设计能够保护配电盘免受电弧影响的电子监控系统。本文将重点讨论电弧行为,而我们的其他论文将讨论其对法医调查和电弧故障保护系统的影响。