首页> 外文期刊>Industry Applications, IEEE Transactions on >Ampacity Calculation for DLO Cable Used in Permanent Installations
【24h】

Ampacity Calculation for DLO Cable Used in Permanent Installations

机译:永久安装中使用的DLO电缆的载流量计算

获取原文
获取原文并翻译 | 示例
           

摘要

DLO is a railroad industry designation given to flexible cables certified for use in diesel locomotives. For use outside the railroad industry, these cables may be labeled with a UL insulation-type certification such as RHW-2. Carried over from the cables' railroad lineage are sizes such as 535 kcmil that are absent from NEC tables. While interpolation of NEC tables may appear as a logical means of calculating ampacity, the NEC limits ampacity calculation options to the formula provided in 310.15(C). Applications of the 310.15(C) formula for cables in underground duct banks are well documented, but constants for duplicating conditions of NEC Table 310.16 are absent from the NEC. For application of nonstandard cable sizes in conditions matching those of NEC Table 310.16, this paper provides ampacity calculations while also clarifying the delineation between permanent building wiring and temporary cords as defined by the NEC.
机译:DLO是铁路行业的一种名称,是经过认证可用于柴油机车的软电缆。为了在铁路行业之外使用,这些电缆可能贴有UL绝缘类型认证,例如RHW-2。从电缆的铁路沿袭而来的是NEC表中没有的诸如535 kcmil的尺寸。虽然NEC表的内插可能是计算载流量的逻辑手段,但NEC将载流量计算选项限制为310.15(C)中提供的公式。 310.15(C)公式在地下导管槽中的电缆上的应用已得到充分证明,但NEC缺少表310.16的重复条件常量。对于在符合NEC表310.16的条件下应用非标准电缆尺寸的情况,本文提供了载流量计算,同时也阐明了NEC定义的​​永久建筑物布线和临时电缆之间的界限。