In industrial facilities with on-site generation, there are two major approaches to connect generators to the main distribution busbar. One is to connect generators through step-up delta-wye transformers with low-resistance grounded wye on the busbar side. The second common method is to connect generators directly to the main distribution busbar and use low-resistance grounding or hybrid grounding in the generator neutral. A grounding resistor in the step-up transformer’s wye side neutral or in the generator neutral will limit the ground fault in the main distribution system. When busbar differential protection is used on the main busbar, sensitivity for bus ground faults has to be evaluated to ensure detection of limited low-level ground faults. While step-up transformer grounding resistors can be selected to allow ground faults of higher magnitudes detectable by bus differential protection, the choice of grounding resistor is more complex when generators are connected directly to the main busbar. In such systems, a grounding resistor in the generator neutral limits the generator fault to protect the alternator core from excessive damage. At the same time, busbar differential protection needs to detect a limited low-magnitude ground fault on the bus. This paper discusses considerations to select the main distribution busbar differential protection type, CTs, and relaying scheme to enable detection of busbar ground faults limited by the generator low-resistance grounding resistor.
机译:在现场发电的工业设施中,有两种将发电机连接到主配电母线的主要方法。一种方法是通过升压三角型变压器将发电机连接到母线侧,并将其与低电阻接地星形星形连接。第二种常见方法是将发电机直接连接到主配电母线,并在发电机中性点使用低电阻接地或混合接地。升压变压器星形Y型中性点或发电机中性点中的接地电阻将限制主配电系统中的接地故障。当主母线上使用母线差动保护时,必须评估母线接地故障的灵敏度,以确保检测到有限的低电平接地故障。虽然可以选择升压变压器接地电阻器以允许通过母线差动保护检测到更高幅度的接地故障,但是当发电机直接连接到主母线上时,接地电阻器的选择更为复杂。在此类系统中,发电机中性点中的接地电阻会限制发电机故障,以保护交流发电机铁芯免受过度损坏。同时,母线差动保护需要检测总线上有限的低幅值接地故障。本文讨论了选择主要配电母线差动保护类型,CT和继电器方案的注意事项,以便能够检测由发电机低电阻接地电阻器限制的母线接地故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号