首页> 外文期刊>Industry Applications, IEEE Transactions on >Considerations for Dependability of the Motor Protection on Current Transformers Performance in VFD Applications
【24h】

Considerations for Dependability of the Motor Protection on Current Transformers Performance in VFD Applications

机译:VFD应用中电动机保护对电流互感器性能的可靠性考虑

获取原文
获取原文并翻译 | 示例
           

摘要

When generators or motors are started via variable frequency drive (VFD), initial frequency is very low, on the order of few hertz, and can be low for a considerable amount of time or even permanently. It is not well recognized in the industry about the consequences of low frequency on current transformers (CTs) performance and how this affects the protection performance as well. First, CTs are designed to operate at the nominal system frequency; however, when operating at low frequency, CTs could saturate at much lower currents; this can happen even at CT nominal current. Second, there are limits of the system frequency measurements in the protective relays, which will impact the correct current magnitude estimation, and therefore, the accuracy of the protection. And finally, protective relays need full power-cycle to measure current; power-cycle will be considerably longer at lower frequency, therefore affecting fault clearance time. This paper will educate engineers on how to consider CTs and protective relay's performance at lower frequencies to ensure adequate protection. It will also explore other solutions to address impact of low frequency on the CTs and protection.
机译:当通过变频驱动器(VFD)启动发电机或电动机时,初始频率非常低,约为几赫兹,并且可能在相当长的时间内甚至永久地处于较低水平。低频对电流互感器(CT)性能的影响及其对保护性能的影响还没有得到业界的认可。首先,CT设计为以标称系统频率运行;但是,当在低频下运行时,CT可能会在低得多的电流下饱和;即使在CT标称电流下也可能发生这种情况。其次,保护继电器中的系统频率测量存在限制,这将影响正确的电流幅度估计,从而影响保护的准确性。最后,保护继电器需要完整的电源循环才能测量电流。在较低的频率下,电源周期会更长,因此会影响故障清除时间。本文将培训工程师如何考虑CT和保护继电器在较低频率下的性能,以确保获得足够的保护。它还将探索其他解决方案,以解决低频对CT和保护的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号