This article proposes an advanced technique for condition assessment of outdoor insulators based on its surface leakage current through employing detrended fluctuation analysis (DFA). Analysis of surface leakage current of in-service insulator can be useful for assessing its surface condition. In the proposed technique, a tracker signal has been developed based on the fundamental component of surface leakage current to extract the distortions from it which carries significant information about contamination level. DFA has then been applied on the extracted distortions of leakage current to estimate its contamination level. In order to investigate experimentally, surface leakage current of 11-kV disc insulator (contaminated at different level) has been captured at different applied voltage level. The proposed technique has been applied on the captured leakage current to estimate contamination level. Results show that employment of the proposed technique provides satisfactory outcomes regarding assessment of insulator condition, which in turn improves the reliability of power system.
机译:本文提出了一种基于其表面泄漏电流的户外绝缘子的条件评估先进技术,通过采用贬值的波动分析(DFA)。在役绝缘体的表面漏电流分析可用于评估其表面状况。在所提出的技术中,已经基于表面漏电流的基本分量开发了跟踪器信号,以从污染水平提取有关污染级别的重要信息的扭曲。然后,DFA已应用于提取的泄漏电流扭曲以估计其污染水平。为了实验研究,在不同的施加电压电平下捕获了11-kV圆盘绝缘体的表面漏电流(在不同水平上污染)。所提出的技术已应用于捕获的漏电流以估计污染水平。结果表明,建议技术的就业提供了关于绝缘体条件的评估的令人满意的结果,这又提高了电力系统的可靠性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号