首页> 外文期刊>IEEE Transactions on Power Electronics >Direct Power Control Applied to Doubly Fed Induction Generator Under Unbalanced Grid Voltage Conditions
【24h】

Direct Power Control Applied to Doubly Fed Induction Generator Under Unbalanced Grid Voltage Conditions

机译:电网电压不平衡条件下双馈感应发电机的直接功率控制

获取原文
获取原文并翻译 | 示例
       

摘要

This paper analyzes the effects of unbalanced voltage on doubly fed induction generators. It also presents a novel control strategy based on direct power control (DPC+) applied to this type of generators, predominant in wind energy applications, that enables them to work under perturbed conditions and achieve optimum results. Although the technique can be implemented to control both rotor converters and grid converters, we will hereby exemplify the former which regulates stator active and reactive power. The results obtained with DPC+ are then compared through experimental tests to indicate that the technique is suitable and achieves good dynamic responses while controlling current distortion, power or torque oscillations. The validation of results has been performed through experimental tests on a 20-kW generator.
机译:本文分析了不平衡电压对双馈感应发电机的影响。它还提出了一种基于直接功率控制(DPC +)的新颖控制策略,该策略主要应用于风能应用中的此类发电机,使它们能够在扰动条件下工作并获得最佳结果。尽管可以实施该技术来控制转子转换器和电网转换器,但是我们在此将举例说明调节定子有功和无功功率的前者。然后将DPC +获得的结果通过实验测试进行比较,以表明该技术是合适的,并且在控制电流失真,功率或转矩振荡的同时实现了良好的动态响应。通过在20 kW发电机上进行的实验测试对结果进行了验证。