Open-Circuit Fault Diagnosis and Fault-Tolerant Control for a Grid-Connected NPC Inverter

机译:并网NPC逆变器的开路故障诊断和容错控制

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents an open-circuit fault detection method for a grid-connected neutral-point clamped (NPC) inverter system. Further, a fault-tolerant control method under an open-circuit fault in clamping diodes is proposed. Under the grid-connected condition, it is impossible to identify the location of a faulty switch by the conventional methods which usually use the distortion of outputs because the distortion of the outputs is the same in some fault cases. The proposed fault detection method identifies the location of the faulty switch and the faulty clamping diode of the NPC inverter without any additional hardware or complex calculations. In the case of the clamping diode faults, the NPC inverter can transfer full rated power with sinusoidal currents by the proposed fault-tolerant control. The feasibility of the proposed fault detection and the fault-tolerant control methods for the grid-connected NPC inverter are verified by simulation and experimental results.
机译:本文提出了一种并网中性点钳位(NPC)逆变器系统的开路故障检测方法。此外,提出了一种在钳位二极管开路故障下的容错控制方法。在并网的情况下,由于在某些故障情况下输出的失真是相同的,因此无法通过通常使用输出失真的常规方法来确定故障开关的位置。提出的故障检测方法无需任何额外的硬件或复杂的计算即可确定NPC逆变器的故障开关和故障钳位二极管的位置。在钳位二极管故障的情况下,NPC逆变器可以通过建议的容错控制以正弦电流传输满额定功率。仿真和实验结果验证了所提出的并网逆变器故障检测和容错控制方法的可行性。