Dynamics of water penetration in mass impregnated cable insulation has been studied. For experimental purposes, artificial damage has been inflicted to a 40-cm-long cable sample and water ingress has been continuously monitored by frequency response measurements. A similar experiment has been conducted on 2.8-m-long cable sample, where both frequency response and time-domain reflectometry (TDR) measurements have been performed. After termination of both experiments, actual moisture content has been measured radially and axially. Based on dielectric measurements, a model of water ingress has been developed and diffusion coefficients have been estimated for mass impregnated cable paper.
机译:研究了浸渗在大量浸渍电缆绝缘中的动力学。出于实验目的,对40厘米长的电缆样本造成了人为破坏,并且通过频率响应测量对进水情况进行了持续监控。已经对2.8米长的电缆样本进行了类似的实验,在该样本中已经执行了频率响应和时域反射法(TDR)测量。在两个实验都终止之后,已经在径向和轴向上测量了实际的水分含量。基于介电测量,已经开发了一种进水模型,并且已经估计了质量浸渍电缆纸的扩散系数。