首页> 外文期刊>IEEE Transactions on Magnetics >Experimental and Numerical Analysis of Stray Field From Transformers
【24h】

Experimental and Numerical Analysis of Stray Field From Transformers

机译:变压器杂散场的实验与数值分析

获取原文
获取原文并翻译 | 示例
       

摘要

We present an assessment of a numerical methodology for evaluating stray fields from transformers by direct comparison with experimental results. The methodology can help to ensure compliance with the limits imposed by national and international laws and regulations on the levels of magnetic fields. We conducted validation experiments on a 1000-kVA cast-resin transformer. All measurements were performed in an anechoic room, in short-circuit conditions, along different directions in space. We compared two different numerical methods, based on linear and nonlinear 3-D finite-element methods, respectively, with the experimental results. Agreement with the measurements was very good. Numerical tools can be considered a valid alternative to measurements for the analysis of the stray magnetic induction field and for the design of shielded devices.
机译:通过与实验结果的直接比较,我们提出了一种评估变压器杂散场的数值方法的评估。该方法可以帮助确保遵守国家和国际法律法规对磁场强度的限制。我们在1000 kVA树脂浇铸变压器上进行了验证实验。所有测量都是在消声室中,在短路条件下,沿着空间的不同方向进行的。我们分别将基于线性和非线性3-D有限元方法的两种不同数值方法与实验结果进行了比较。与测量的一致性非常好。可以将数字工具视为测量的有效替代方法,用于分析杂散磁感应场和设计屏蔽设备。