摘要

The paper begins with a review of techniques for computer based protection of multi-winding three-phase power transformers. After reviewing the principles of harmonic-restraint and voltage-restraint current differential protection, the paper develops a technique which computes and uses flux-current relationship of the transformer to obtain the restraint function. It is shown that this protection technique requires fewer computations as compared to the harmonic current computation, and hence can be implemented on a microcomputer of modest capability. The principle has been tested in the laboratory on a model power transformer. The relay based on this flux-restraint principle performs well on all the system phenomena simulated in the laboratory. It is expected that a relay based on this principle will be tested in the field on a power transformer.
机译:本文首先回顾了基于计算机的多绕组三相电力变压器保护技术。在回顾了谐波抑制和电压抑制电流差动保护原理之后,提出了一种计算和利用变压器的磁通-电流关系来获得抑制功能的技术。结果表明,与谐波电流计算相比,这种保护技术所需的计算更少,因此可以在性能适中的微型计算机上实现。该原理已在实验室的模型电源变压器上进行了测试。基于这种磁通约束原理的继电器在实验室中模拟的所有系统现象上均表现良好。预计将基于此原理的继电器在电力变压器上进行现场测试。