The industrial problem of the air-side fouling of compact heat exchangers has been studied in a laboratory wind tunnel for particles in the μm to mm range. The measurements of pressure drop across the exchanger as well as the quantification and classification of the particles blocked by and passing through it were taken for discrete ranges of particle sizes. Observation showed that the blocked particles either drop to the wind tunnel floor, remain on the outside surface of the exchanger (falling to the floor once the wind velocity drops), or penetrate a short distance into it according to the relative values of fin spacing and particle size. These last are the most detrimental to exchanger performance. There is a critical particle size for which this penetration is maximal. A brief non-dimensional geometrical analysis allows one to predict this critical size range for any finned exchanger. It has been found to be between 0.5-0.7 times the diameter of the largest sphere that can be inscribed between the fins. Confirmation of this was found with a second exchanger. The addition of humid conditions within the tunnel or on the exchanger itself did not modify these values. Subtracting the pressure drop due to the clean exchanger from the total measured value confirms that the foulant acts like an extra mechanical filter in series with the exchanger. This is quite understandable given the short penetration length of the particles (up to 3 mm). Finally, the effects of a closed wind tunnel test section on the measurements for non-isothermal conditions in the exchanger are discussed.
机译:紧凑型换热器的空气侧结垢的工业问题已在实验室风洞中研究,其粒径在μm至mm之间。对于离散的粒径范围,进行了跨交换器的压降的测量以及被交换器阻塞和通过的颗粒的定量和分类。观察表明,被阻塞的颗粒要么落到风洞地板上,要么留在交换器的外表面上(一旦风速下降就掉落到地板上),或者根据翅片间距和粒度。最后这对交换器性能最不利。有一个临界颗粒尺寸,此渗透最大。简短的无量纲几何分析使您可以预测任何翅片式换热器的临界尺寸范围。已经发现它的直径是可在鳍片之间接缝的最大球体直径的0.5-0.7倍。用第二个交换器发现了这一点。在隧道内或交换器本身上增加潮湿条件不会改变这些值。从总测量值中减去由于清洁的交换器而引起的压降,可以确认污垢就像交换器串联的额外机械过滤器一样起作用。考虑到颗粒的穿透长度很短(最大3 mm),这是完全可以理解的。最后,讨论了封闭式风洞测试部分对换热器非等温条件测量的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号