Comparison between traditional single-phase auto reclosing and adaptive technique based on harmonic content measurement

机译:传统单相重合闸与基于谐波含量测量的自适应技术的比较

获取原文
获取原文并翻译 | 示例
           

摘要

This study presents the results of single-phase auto reclosing technique tests, comparing the performance of traditional procedure and fast adaptive procedure. The last is based on the measurement of voltage harmonic content on the transmission line faulty phase terminals. The transmission system used was modelled on the real-time digital simulator with a distance relay and a quality meter to more realistically implement the reclosing techniques. The studied system was based on an actual Brazilian 500 kV transmission system. This study highlights the advantages of using the adaptive technique opposite to the use of traditional manoeuvre.
机译:这项研究提出了单相自动重合闸技术测试的结果,比较了传统程序和快速自适应程序的性能。最后一种基于对传输线故障相端子上的电压谐波含量的测量。所使用的传输系统是在带有距离继电器和质量计的实时数字仿真器上建模的,以更实际地实现重合闸技术。研究的系统基于实际的巴西500 kV输电系统。这项研究突出了使用自适应技术与传统操作相反的优势。