首页> 外文期刊>Generation, Transmission & Distribution, IET >Centralised busbar differential and wavelet-based line protection system for multi-terminal direct current grids, with practical IEC-61869-compliant measurements
【24h】

Centralised busbar differential and wavelet-based line protection system for multi-terminal direct current grids, with practical IEC-61869-compliant measurements

机译:适用于多端子直流电网的集中式母线差动和基于小波的线路保护系统,具有符合IEC-61869的实际测量值

获取原文
获取原文并翻译 | 示例
           

摘要

This study presents a method for discriminative detection of direct current (DC) faults on voltage source converter-powered multi-terminal high-voltage direct current transmission systems using two fundamental guiding principles, namely instantaneous current-differential and travelling waves. The proposed algorithm utilises local voltage and current measurements from all transmission lines connected to a DC busbar, and current measurement from the DC side of the converter. The scheme operates at a sampling frequency of 96 kHz, which conforms with IEC 61869-9. No long distance communication is involved while measurements and signal exchange within DC substations are enabled by the utilisation of IEC 61850. Performance is assessed firstly through detailed transient simulation, using verified models of modular multi-level converters, hybrid DC circuit breakers and inductive DC-line terminations. Furthermore, practical performance and feasibility of the scheme are evaluated through laboratory testing, using the real-time Opal-RT hardware prototyping platform. Simulation and experimental results demonstrate that the proposed protection algorithm can effectively, and within a very short period of time (i.e. <;1 ms), discriminate between busbar and line faults (internal faults), while remaining stable during external faults. Additionally, it has been demonstrated that IEC 61869-9 is suitable for enabling fast DC protection schemes incorporating travelling waves.
机译:这项研究提出了一种判别检测电压源转换器供电的多端子高压直流输电系统上的直流(DC)故障的方法,该方法使用两种基本的指导原理,即瞬时电流差动波和行波。所提出的算法利用了连接到直流母线的所有传输线的本地电压和电流测量值,以及转换器直流侧的电流测量值。该方案以96 kHz的采样频率运行,符合IEC 61869-9。通过使用IEC 61850可以在DC变电站内进行测量和信号交换时不涉及长距离通信。首先,通过详细的瞬态仿真,使用经过验证的模块化多电平转换器,混合式DC断路器和感应式DC-S模型,评估性能。线路终端。此外,使用实时Opal-RT硬件原型平台,通过实验室测试评估了该方案的实际性能和可行性。仿真和实验结果表明,提出的保护算法可以在很短的时间内(即<; 1 ms)内有效地区分母线和线路故障(内部故障),同时在外部故障期间保持稳定。此外,已证明IEC 61869-9适用于启用包含行波的快速DC保护方案。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号