Testing of a hydropower plant's stability and performance using PMU and control system data in closed loop

机译:使用PMU和闭环控制系统数据测试水电厂的稳定性和性能

获取原文
获取原文并翻译 | 示例
           

摘要

In response to recent concerns regarding deteriorating frequency quality in the Nordic power system, the Nordic transmission system operators have developed draft requirements for the provision of frequency containment reserves (FCR). These requirements outline extensive tests, which the power plant owners must perform to qualify to deliver FCR. In this study, the authors demonstrate that one can check these requirements by standard system identification techniques while the plant is in normal operation and by using measurements readily available from the plant's control system or from a phasor measurement unit (PMU). The validity of the proposed method is demonstrated using Monte Carlo Simulation, where they investigate the effects of the main assumption and potential non-linearities affecting the approach. Data from real power system operation is used to demonstrate the performance of the method.
机译:为了响应最近有关北欧电力系统中频率质量恶化的担忧,北欧传输系统运营商已制定了有关提供频率限制储备(FCR)的要求草案。这些要求概述了广泛的测试,电厂所有者必须执行这些测试才能有资格交付FCR。在这项研究中,作者证明了可以在工厂正常运行时通过标准的系统识别技术并通过使用工厂的控制系统或相量测量单元(PMU)提供的测量来检查这些要求。蒙特卡罗模拟证明了所提出方法的有效性,他们在其中研究了主要假设的影响以及可能影响方法的非线性。来自实际电力系统运行的数据用于证明该方法的性能。