An Experimental Determination of a Real Fire Performance of a Non-Load Bearing Glass Wall Assembly

机译:非承重玻璃幕墙组件真实防火性能的实验确定

获取原文
获取原文并翻译 | 示例
       

摘要

A glass wall assembly was exposed to an intense real-scale compartment fire. The wall assembly consisted of four glass sections, two of which were fitted with tempered double-pane glass and the other two sections were fitted with tempered single-pane glass. At each glass section, temperatures were measured at the exposed face and the unexposed face. Total heat flux gauges were used to measure both the temporal variation of the energy incident on the glass wall and the transmitted energy rate detected through two of the glass sections. Visual and infrared cameras were used to image the unexposed face of each wall assembly during the fire exposure. Results of glass breakage and subsequent glass fall out were compared to studies in the literature for glass sections exposed to compartment fires. The behavior of the glass wall assembly under a fire load is presented.