The experimental program described in this paper sought to assess the suitability of the small scale DEF(AUST)5706 standard for measuring the suppression and burnback performance of Class B foams on pool fires. DEF(AUST)5706 is an Australian Defence standard mandatory for use by the Australian Navy, Army and Air Force. The test protocol required the measurement of the 3/4 control, extinguishment and 1/3 burnback times for a circular pan of aviation gasoline (AVGAS 100/130), 0.28 m2 in surface area. The test program involved compressed-air foams (CAF) and aspirated foams of two expansion ratios, and employed two AFFF formulations: a 6% telomer concentrate and, to obtain base-line measurements, 3% PFOS FC-600 concentrate which was manufactured by the 3 M company prior to the PFOS phase out. At lower expansion (7:1), the aspirated and compressed-air foams demonstrated similar fire control performance, whilst more expanded (9:1) CAF was generally more efficient at extinguishing, but less efficient in controlling the fire. CAF formed a better seal over the fuel surface and at the hot pan walls, and these foams performed noticeably better than aspirated foam against fuel re-ignition. The paper links these observations with the underlying distributions of bubble sizes, which were measured and fitted to modified Rosin/Rammler cumulative volume distribution functions. We propose that a modified version of DEF(AUST)5706 be adopted as a universal small-scale test protocol.
机译:本文所述的实验程序旨在评估小型DEF(AUST)5706标准在测量池火上B类泡沫的抑制和回燃性能方面的适用性。 DEF(AUST)5706是澳大利亚海军,陆军和空军强制使用的澳大利亚国防标准。测试规程要求测量表面积为0.28平方米的圆形航空汽油(AVGAS 100/130)的3/4控制,灭火和1/3回燃时间。该测试程序涉及两种膨胀率的压缩空气泡沫(CAF)和吸气泡沫,并采用了两种AFFF配方:6%端粒浓缩物和(为获得基线测量结果)3%PFOS FC-600浓缩物,该浓缩物由PFOS淘汰之前的3 M公司。在较低的膨胀比(7:1)下,吸气和压缩空气泡沫具有相似的防火性能,而在膨胀率更高(9:1)的情况下,CAF扑灭火焰的效率更高,但控制火焰的效率更低。 CAF在燃油表面和热锅壁上形成了更好的密封,这些泡沫在防止燃油重燃方面比吸气泡沫明显更好。本文将这些观察结果与气泡大小的基本分布联系起来,对这些气泡大小的分布进行了测量并拟合到修改后的Rosin / Rammler累积体积分布函数中。我们建议采用DEF(AUST)5706的修改版本作为通用的小型测试协议。

著录项

  • 来源
    《Fire Technology》 |2011年第1期|p.149-162|共14页
  • 作者单位

    Process Safety and Environment Protection Research Group,School of Engineering, The University of Newcastle, Callaghan,NSW 2308, Australia;

    Process Safety and Environment Protection Research Group,School of Engineering, The University of Newcastle, Callaghan,NSW 2308, Australia;

    Process Safety and Environment Protection Research Group,School of Engineering, The University of Newcastle, Callaghan,NSW 2308, Australia;

    Process Safety and Environment Protection Research Group,School of Engineering, The University of Newcastle, Callaghan,NSW 2308, Australia;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    fire suppression; firefighting foams; petroleum fires; lastfire; suppression of class B fires;